@@ -1176,21 +1176,32 @@ \section{Flame Tilt}
1176
1176
1177
1177
\clearpage
1178
1178
1179
-
\section{Fireball Diameter}
1179
+
\section{Fireball Diameter and Height}
1180
1180
\label{FireballDiameter}
1181
+
\label{FireballHeight}
1181
1182
1182
-
A fireball is caused by a sudden, violent rupture of a container containing volatile liquids or gases, typically under high pressure. Figure~\ref{Fireball_Diameter_Scatterplot} summarizes comparisons of the measured and predicted maximum horizontal fireball diameter of several sets of experiments.
1183
+
A fireball is caused by a sudden, violent rupture of a container containing volatile liquids or gases, typically under high pressure. Figure~\ref{Fireball_Diameter_Scatterplot} summarizes comparisons of the measured and predicted maximum horizontal fireball diameter of several sets of experiments. Figure~\ref{Fireball_Height_Scatterplot} summarizes comparisons of the measured and predicted fireball heights; that is, the height of the fireball at the time of maximum diameter.
Copy file name to clipboardExpand all lines: Manuals/FDS_Validation_Guide/Species_Chapter.tex
+1-1Lines changed: 1 addition & 1 deletion
Original file line number
Diff line number
Diff line change
@@ -1875,7 +1875,7 @@ \subsection{NIST Pool Fires}
1875
1875
\subsection{Utiskul Compartment}
1876
1876
\label{sec:Utiskul_Compartment}
1877
1877
1878
-
A summary of the experiments is given in Sec.~\ref{Utiskul_Compartments_Description}. Figures~\ref{Utiskul_1} through \ref{Utiskul_4} display comparisons of measured and predicted compartment and ceiling jet temperatures, pressure, heat flux, and species concentration. The fuel mass loss rate is specified, not predicted, by the model.
1878
+
A summary of the experiments is given in Sec.~\ref{Utiskul_Compartment_Description}. Figures~\ref{Utiskul_1} through \ref{Utiskul_4} display comparisons of measured and predicted compartment and ceiling jet temperatures, pressure, heat flux, and species concentration. The fuel mass loss rate is specified, not predicted, by the model.
1879
1879
1880
1880
The species concentrations are measured at extraction points 2~cm above the floor and 2~cm below the ceiling, 10~cm from the vents along the compartment centerline. The ceiling jet temperatures are taken 2~cm below the ceiling along the centerline, at locations 2.5~cm from the upper vent (TC2), 2.5~cm from the back wall (TC13), and at the ceiling center (TC17). The pressures are taken 1.5~cm above the floor and below the ceiling, 2.5~cm from the side wall, and 5~cm from the front wall, where the vents are located.
0 commit comments